www.chino.vn
KINH DOANH BỘ GHI, BỘ ĐIỀU KHIỂN HIỂN THỊ,
NHIỆT KẾ HỒNG NGOẠI,
ĐỒNG HỒ VÀ CẢM
BIẾN ĐO NHIỆT ĐỘ VÀ ĐỘ ẨM,
BỘ ĐIỀU CHỈNH
NGUỒN THYRISTOR HÃNG CHINO
Email: info@chino.vn
Tel: 0944577466

Instrumentation, Control and Systems

RECORDERS |
||||
CONTROLLERS |
||||
RADIATION THERMOMETERS |
||||
MOISTURE METERS |
||||
SENSORS |
||||
THYRISTOR REGULATORS |
||||
TRACEABILITY |

CHINO CORPORATION
GRAPHIC RECORDER |
||||
KR3000 SERIES |
KR3000 Series are network-compatible paperless recorders with high visibility 12.1" TFT color LCD display and touch panel operation system. High speed of sampling rate 100ms for 48 points and high accuracy of ±0.1% were realized, and measured data is stored into internal memory and maximum 8GB compact flash card (CF card).
As it can be monitored by a web browser display on several computers on intranet or internet, FTP transfer of data file and E-mail notification are also available.
Large sized 12.1" TFT color LCD display
Large capacity of data memory and various recording method
Multi points recording with high speed/high accuracy
Main Specifications |
Measuring points : | 12, 24, 36 and 48 channels |
Input types : |
DC voltage 10 kinds, DC current (with external shunt resistor), Thermocouple 16 kinds, Resistance thermometer 4 kinds |
Accuracy ratings : | ±0.1%±1 digit (DC voltage) |
Rated power voltage : | 100 to 240V AC, 50/60Hz |
Communications : | Ethernet, RS232C, RS422A/RS485 (option) |
.png)
GRAPHIC RECORDER |
||||
KR2000 SERIES |
KR2000 Series are network-compatible paperless recorders with high performance and high operating function employed high visibility 5.6"TFT color LCD display. High speed of sampling rate 100ms for 12 points and high accuracy of ±0.1% were realized, and measured data is stored into internal memory and maximum 8GB compact flash card. As it can be monitored by a web browser display on several computers on intranet or internet, FTP transfer of data file and E-mail notification are also available.
The recorder can be used for various applications such as data management, research, development, remote and wide range monitoring by utilizing internet environment.
6 or 12 channels measurement at sampling rate of 100ms
Simple no-manual operations. Large data memory
Standard Ethernet connectivity
Main Specifications |
Measuring points : | 6 or 12 channels |
Input types : |
DC voltage 10 kinds, Thermocouple 35 kinds Resistance thermometer 8 kinds DC current (shunt resistors) |
Accuracy ratings : | ±0.1% ± 1 digit (DC voltage) |
Rated power voltage : | 100 to 240V AC, 50/60Hz |
Communications : | Ethernet, RS232C, RS422A/RS485 (option) |
1
.png)

UBIQUITOUS RECORDER |
||||
KR5000 SERIES |
KR5000 series is a high performance network-based recorder acquiring and logging measurement field data up to 128 channels. Real time trends with web browser can be monitored from any PC connected to the internet and intranet with no software installation. Measured data automatically transferred to a server with e-mail and FTP client function support
The recorder can be used for various applications such as data management, research, development, remote and wide range monitoring by utilizing internet environment.
Monitoring screen designed in the html form
No software application needed
Variety of display modes; vertical/horizontal trend digital data, bar graph, alarm condition, group display of 8 screens in one
E-mail notification at the time of alarm generating
MODBUS instrument, field scanner, recorder and controller are connectable
Main Specifications |
Input points : | Up to 128 points of registered data |
Input interval : |
1 second/all points |
Group register : | Group name, connected instruments number, tag name, unit, input operate (moving average, arithmetic expression) |
Trend display : | Real time or historical trend display |
Bar graph : | Selectable from horizontal and vertical |
Data display : | Data value display and alarm status (the color is selectable) |
Screen partition display : | Screen partition to a maximum of 8 |
Overview : | Display measuring data, Alarm status. Renew each 10 seconds. |
Information display : | Alarm, message, file list, etc Setting screen : Ethernet; FTP; E-mail; User ID; Input instrument; clock |
.png)
.png)
180mm HYBRID RECORDERS |
||||
AH3000 SERIES |
The recorders conforming to CE-marking, UL and CSA are 180mm hybrid recorders for 6-point, 12-point, 24-point types and 1 to 4-pen types with a simultaneous display of multi-channel data, bargraph display and other unique features.
Simultaneous digital displays of multi-point data
Universal input
The MODBUS communications
Package software "KIDS" for data acquisition
Number of measuring points: | |
Input signal: | 6 points, 12 points, 24 points 1 pen, 2 pens, 3 pens, 4 pens DC voltage (±118mV to ±50V) DC current (Adding shunt resistors) Thermocouple (B, R, S, N, K, E, J, T, others) Resistance thermometer (Pt100, JPt100, others) |
Accuracy rating: | ±0.1% ±1 digit (DC voltage input) |
Chart speed: | 1 to 1500mm/h (dotting type) 1 to 600mm/h, 1 to 200mm/mim (pen types) |
Power supply: | 100 to 240VAC |
Communications: | RS232C, RS422A, RS485 (option) |
Dimensions: | 288X 288X 247mm |
100mm HYBRID RECORDERS |
||||
AL3000 SERIES |
The recorders conforming to CE-marking, UL and CSA are 100mm hybrid recorders for 6-point type and 1 to 4-pen types with a simultaneous display of multi-channel data, bargraph display and other unique features. A software package "KIDS" for data processing of measured values is available.
Simultaneous digital displays of multi-point data
Universal input
MODBUS communications
Main Specifications |
Number of measuring points: | |
Input signal: | 6 points 1 pen, 2 pens, 3 pens, 4 pens DC voltage (±118mV to ±50V) DC current (Adding shunt resistors) Thermocouple (B, R, S, N, K, E, J, T, others) Resistance thermometer (Pt100, JPt100, others) |
Accuracy rating: | ±0.1% ±1 digit (DC voltage input) |
Chart speed: | 1 to 1500mm/h (dotting type) 1 to 600mm/h, 1 to 200mm/mm (pen types) |
Power supply: | 100 to 240VAC |
Communications: | RS232C, RS422A, RS485 (option) |
Dimensions: | 144X 144X 243mm (6-points/285mm (1 to 4-pen) |
250mm HYBRID |
||||
RECORDER |
||||
LE5000 SERIES |
.png)
LE5000 series are 250mm hybrid recorders with multi-range input. Innovative design high performance recorder provides high accuracy, ±0.05%; high speed sampling, 0.1 second for 36 points and high speed recording, 3 seconds/line. Simple operational keys and PC setting functions drastically improved usability of recording system.
High speed sampling at 0.1 sec for 36 points and high-speed recording
Operation keys are functionally designed for ease of use
High accuracy of 0.05%
Main Specifications |
Number of measuring points: | 12, 24 or 36 channels |
Input signals: | DC voltage 8 kinds, Thermocouple 28 kinds, Resistance thermometer 8 kinds, DC current (shunt resistors) |
Accuracy ratings: | ±0.05% +1 digit (DC voltage) |
Rated power voltage: | 100 to 240V AC, 50/60Hz |
Communications: | Ethernet, RS422A, RS485 (option) |
60mm ELECTRONIC RECORDERS |
||||
ES600 SERIES |

1-point, 2-point, 3-point, 6-point dotting type and 1-pen types are available in the recorders.
Small and light-weight (depth-200mm)
Reliable self-balancing type
2
100mm HYBRID RECORDERS |
||||
EL3000 SERIES |

1-point, 2-point, 3-point, 6-point dotting types and 1 to 3-pen types are available
Small and light-weight
Various models and options
180mm ELECTRONIC RECORDERS |
||||
EH SERIES |

1 to 12-point, dotting types and 1 to 3-pen types are available.
Various options for many applications
High accuracy on 180mm industrial recorders
Robust analog recorders
DIGITAL |
||||
INDICATING |
||||
CONTROLLERS |
||||
LT450 / LT470 |
.png)
96X96mm
The digital indicating controllers feature all functions, which are necessary for various control applications, including newly developed PID algorithms and a learning type overshoot suppression function "JyroNavi".
Easy view and simple operation by large LED displays and large switches
Universal input
MODBUS communications protocol
Conformance to CE, UL and CSA
Front panel conforming to NEMA4X (IP66) water and dust protection (option)
Main Specifications |
Input signal: | DC voltage (0 to 20mV, 0 to 5V, 0 to 10V) DC current (4 to 20mA by adding a shunt resistor) Thermocouple (B, R, S, N, K, E, J, T, U, L) Resistance Thermometer (Pt100, JPt100) |
Accuracy rating: | ±0.1% of scale range ±1 digit |
Control system: | PID system (2-position control is available) |
Output type: | On-off pulse, SSR-drive pulse, current output, on-off servo, voltage output |
Auto-tuning: | Standard |
Overshoot suppression function: | |
On/off selectable | |
Power supply: | 100 to 240VAC, 50/60Hz |
Dimensions: | 48X96X 132mm (LT450), 96X96X 132mm (LT470) |
DIGITAL |
||||
INDICATING |
||||
CONTROLLERS |
||||
LT350 / LT370 |
.png)
96X96mm
The digital indicating controllers feature all functions, which are necessary for various control applications, including newly developed PID algorithms and an overshoot suppression function.
Easy view and simple operation by large LED displays and large switches
Universal input
MODBUS communications protocol
Conformance to CE, UL and CSA
Front panel conforming to NEMA4X (IP66) water and dust protection (option)
Main Specifications |
Input signal: | DC voltage (0 to 5V) DC current (4 to 20mA by adding a shunt resistor) Thermocouple (B, R, S, N, K, E, J, T, U, L) Resistance Thermometer (Pt100, JPt100) |
Accuracy rating: | ±0.25% of scale range ±1 digit |
Control system: | PID system (2-position control is available) |
Output type: | On-off pulse, SSR-drive pulse, current output, voltage output |
Auto-tuning: | Standard |
Overshoot suppression function: | |
On/off selectable | |
Power supply: | 100 to 240VAC, 50/60Hz(24VDC, option) |
Dimensions: | 48X96X132mm (LT350), 96X96X132mm (LT370) |
DIGITAL INDICATING |
||||
CONTROLLERS |
||||
LT230 |
.png)
The digital indicating controllers feature many functions including newly developed PID algorithms and an overshoot suppression function.
Universal input
MODBUS communications protocol
Conformance to CE, UL and CSA
Front panel conforming to NEMA4X (IP66) water and dust protection (option)
Main Specifications |
Input signal: | DC voltage (0 to 5V) DC current (4 to 20mA by adding a shunt resistor) Thermocouple (B, R, S, N, K, E, J, T, U, L) Resistance Thermometer (Pt100, JPt100) |
Accuracy rating: | ±0.25% of scale range ±1 digit |
Control system: | PID system (2-position control is available) |
Output type: | On-off pulse, SSR-drive pulse, current output, voltage output |
Auto-tuning: | Standard |
Overshoot suppression function: | |
On/off selectable | |
Power supply: | 100 to 240VAC, 50/60Hz(24VDC, option) |
Dimensions: | 48X48X122mm |
3
DIGITAL INDICATING |
||||
CONTROLLERS |
||||
LT110 |
.png)
The digital indicating controllers feature many functions including PID auto-tuning function for various control applications in compact size of 48X 24mm.
Compact lightweight and space-saving type for downsizing equipment or panel board
Multi-input of thermocouples and resistance thermometers
Conformance to CE
Front panel conforming to IP65 (IEC) water and dust protection
Main Specifications |
Input signal: | Thermocouple (K, J, E, N) Resistance thermometer (Pt100,JPt100) |
Accuracy rating: | Thermocouple ±0.3% of scale range ±1 digit or ±2°C, whichever larger) Resistance thermometer (±0.2% of scale range ±1 digit) |
Control system: | PID system (2-position is available) |
Output type: | On-off pulse, SSR-drive pulse, current output |
Auto-tuning: | Standard |
Power supply: | 100 to 240VAC, 50/60Hz |
Dimensions: | 48X24X110.5mm |
DIGITAL INDICATING |
||||
CONTROLLER |
||||
DB SERIES |
.png)
The DB series is a 96 X 96mm digital indicating controller with the indicating accuracy of ±0.1% and the control cycle of approximately 0.1 seconds.
Various functions including universal input and multiple setting values (8 types) are provided as standard.
Large easy-to-view 5-digit display
Highly-functional operation screen and settings screen
Outstanding controllability
Conforming to international safety standards and European directives (CE) and conforming to RoHS
Main Specifications |
Input type: | Thermocouple (B, R, S, K, E, J, T, N, others) Resistance thermometer (Pt100, Pt-Co, others) DC voltage (±10nnV, ±20mV, ±50mV, ±100mV, ±5V, ±10V) DC current (0 to 20mA) |
Accuracy rating: | ±0.1% of measuring range ±1 digit |
Control system: | PID system |
Output type: | ON-OFF pulse, ON-OFF servo, Current output, SSR drive pulse, Voltage output |
Power supply: | 100 to 240VAC or 24VAC/24VDC |
Communication interface: | |
RS232C, RS422A, RS485 (option) | |
Dimensions: | 96X96X127mm |
DIGITAL |
||||
PROGRAM |
||||
CONTROLLER |
||||
KP SERIES |
.png)
The KP series is a 96 X 96mm digital program controller with the indicating accuracy of ±0.1%, the control cycle of approximately 0.1 seconds and maximum 19 program patterns (maximum 19 steps/pattern).
Various functions including the whole program pattern display screen and universal input are provided as standard.
Large easy-to-view 5-digit display
Highly-functional operation screen and settings screen
Easily identifiable pattern progress display
Outstanding controllability
Conforming to international safety standards and European directives (CE) and conforming to RoHS
Main Specifications |
Input type: | Thermocouple (B, R, S, K, E, J, T, N, others) Resistance thermometer (Pt100, Pt-Co, others) DC voltage (±10nnV, ±20mV, ±50mV, ±100mV, ±5V, ±10V) DC current (0 to 20mA) |
Accuracy rating: | ±0.1% of measuring range ±1 digit |
Control system: | PID system |
Output type: | ON-OFF pulse, ON-OFF servo, Current output, SSR drive pulse, Voltage output |
Power supply: | 100 to 240VAC or 24VAC/24VDC |
Communication interface: | |
RS232C, RS422A, RS485 (option) | |
Dimensions: | 96X96X127mm |
GRAPHIC |
||||
PROGRAM |
||||
CONTROLLER |
||||
DP-G SERIES |
.png)
The DP-G series is a graphic program controller employed high visibility 5.6" TFT color LCD display. Maximum 200 types of program pattern (Maximum 4000 steps) are stored and performance pattern is selectable.
Easy program pattern settings on graphic screen
High performance and universal input
Storing settings in CF card
Main Specifications |
Input signal: | Thermocouple (B, R, S, N, K, E, J, T, others) Resistance Thermometer (Pt100, JPt100, others) DC voltage (±10mV, ±20mV, ±50mV, ±100mV, ±5V, ±10V) DC current (20mA) |
Accuracy rating: | ±0.1% of measuring range ±1 digit (DC voltage / current input) |
Control system: | PID system |
Output type: | ON-OFF pulse type, ON-OFF servo type, current output type, SSR drive pulse type, voltage output type |
Power supply: | 100 to 240V AC, 50/60Hz |
Dimensions: | 144X144X252mm |
DIGITAL INDICATING |
||||
CONTROLLERS |
||||
LT830 SERIES |
.png)
The digital indicating controller features various functions including socket type terminal board, 24V AC/DC power supply, international compliance, and MODBUS protocol communication. The software package provides the ease of parameter setup and data monitoring.
Universal input
PID Algorithms for easy operation
User friendly LED numerical display
Conformance to CE, UL and CSA
KIDS and PASS software
Main Specifications |
Input signal: | Thermocouple (B, R, S, N, K, E, J, T) Resistance Thermometer (Pt100) |
Accuracy rating: | ±0.3% of measuring range ±1 digit (at reference operation conditions) |
Control system: | On-off pulse type PID system, SSR drive type PID system |
Auto-tuning: | Standard (manual setting of PID constants enabled) |
Overshoot suppression: | |
ON/OFF selectable | |
Power supply: | 100 to 240V AC, 50/60Hz |
Dimensions: | 48X48X80mm |
4
ON-LINE INFRARED RADIATION |
||||
THERMOMETER |
||||
IR-SA SERIES |
.png)
The IR-SA series of Infrared Radiation Thermometer provides broad selection of small and robust units to match your on-line applications for non-contact temperature measurement from 0 to 2500°C under harsh environment. Four models are available with modbus connectivity for parameter setup through remote setting unit or PC.
Withstand temperature 90°C, IP67, CE approval
Fast response time of 0.002 seconds for IR-SAI/IR-SAS
RS485 modbus connectivity
Telescope or laser pointer for targeting
HIGH-SPEED |
||||
RADIATION |
||||
THERMOMETER |
||||
IR-CA SERIES |
.png)
The IR-CA Product Line of Non-Contact Infrared Thermometers provides broad selection of units to match your applications and requirements for non-contact temperature measurement. The product line consists of 15 different series grouped into General Purpose and Application Specific models.
Functional digital display and parameter setup keys
High accuracy, high-speed response, high reliability
High distance factor in focusable model to enable ease of installation
Optional RS485 communications
Remote setup and monitoring by IR-GZ connectable upto 32 IR-CA
Software package IR-VXC1E
Variety of accessories to protect the IR-CA under harsh environment
FIBER OPTIC RADIATION |
||||
THERMOMETER |
||||
IR-FA SERIES |
.png)
The IR-FA series is a fiber optic radiation thermometer featuring multi-function and high-speed response (10ms). Three types: single-color type for low temperature; single-color type for medium/high temperature and two-color type, are available.
Low temperature type with high-speed response and short wavelength enables to measure objects with low emissivity like as metals.
Medium/high temperature type with high accuracy (±0.5 to 1% for 1000 to 2000°C) and high-speed response is for various temperature measurement fields.
Two-color type is stable with less effectiveness of smoke, vapor, dust and lack-of-view.
Main Specifications |
Detecting element/measuring wavelength: | ||
Single-color type: | PbS/2.0 p m, InGaAs/1.55 p m, Si/0.9 p m, | |
Two-color type: | Hybrid element 0.9/1.55 pm, | |
Output : | 4 to 20mADC | |
Power supply: | 24VDC |
5
INFRARED RADIATION |
||||
THERMOMETERS |
||||
IR-BA SERIES |
.png)
The IR-BA series is a non-contact and high-speed compact radiation thermometer. The card sized detector with built-in converting function of 4-20mA output signal can easily be installed in narrow places, production lines and small equipment.
A standard speed type and a high speed type 150ms/95%) are respectively available for these standard type and small-target/short-distance type and small-target/long-distance type, and also various applicable types like as glass, lamp-anneal, film and burning gas.
High response: Standard : 100ms, High-speed : 50ms
Compact & light-weight : W32 X H56 X D100mm, 220g
Main Specifications |
Detecting element/measuring wavelength: Thermopile | ||
Measuring range: | 0 to 300°C, 0 to 600°C | |
Output: | 4 to 20mADC | |
Power supply: | 12 to 24VDC |
THERMAL IMAGING |
||||
SENSOR |
||||
TP-L Series |
.png)
The TP-L series is a compact infrared thermal imaging sensor utilizing a thermopile array detector.
Easy to Use and Implement
2000 pixel Resolution
Built-In Alarms
IP65 / NEMA4
Main Specifications |
Temperature range: | —20 to 300°C |
Resolution: | 0.5°C (At black body temperature of 100°C ) |
Accuracy: | ±2% of reading or ±3°C whichever lager (At ambient temp of 25°C ±2°C) |
Power supply : | 12 to 24V DC |
HANDHELD TYPE |
||||
INFRARED RADIATION THERMOMETERS |
||||
MODEL IR-TA |
Simple temperature measurement by pinpointing center of measuring spot by laser. Automatic back-lit LCD display at dark places by brightness sensor.
CE-marking (option)
Main Specifications (single-color types) |
Detecting element: | Thermopile |
Measuring range: | -40 to 500°C |
Power supply: | AA battery, 2 pcs |
ON-LINE MEASUREMENT OF INFRARED MULTI ANALYZER, MOISTURE (THICKNESS) METERS
INFRARED MULTI ANALYZER |
||||
IM SERIES |
||||
MIRROR TYPE |
||||
FIBER TYPE |
.png)
The IM series is on-line multi analyzer utilizing the infrared absorption. Converting capabilities are built into the compact designed detector unit for easy installation and operation.
Up to 10 wavelength, capable of measuring 4 constituents.
Ethernet, MODBUS communications.
High-speed & High-repeatability (28ms).
Self-diagnostic function, easy maintenance.
Main Specifications |
Measuring system: | Infrared reflection type |
Measuring wavelength: | Up to 10 wavelengths |
Measuring scope: | Up to 4 constituents |
Computing function: | Ratio calculation for 2-color or 3-color, and multiple regression calculation |
Calibration curve: | Linear, quadratic, cubic and multiple regression line |
HANDHELD TYPE |
||||
RADIATION |
||||
THERMOMETERS |
||||
IR-H SERIES |
.png)
The handheld thermometer is a small and lightweight with a clear view-finder. The direct view-finder enables to measure a small object with a long distance.
Temperature range from 400°C to 3000°C (IR-HQH)
CE-marking
Low temperature area and emissivity are measured by connecting a K-type thermocouple separately prepared.
Main Specifications |
Detecting element: | Si (IR-HS), InGaAs (IR-HI), Si/InGaAs (IR-HQH) |
Response time: | 0.2 seconds |
Power supply: | AA battery, 2 pcs |
HANDHELD TYPE |
||||
DIGITAL RADIATION |
||||
THERMOMETERS |
||||
IR-AH SERIES |
.png)
The handheld thermometer offers a wide measuring range of 600°C to 3000°C for IR-AHS, 900°C to 3000°C for IR-AHU, and —50°C to 1000°C for IR-AHT digital display of the measured value in view-finder and LCD display, plus storage of measured data.
A data logging software package for easy data treatment
CE-marking
Main Specifications |
Detecting element: | Si, Thermopile |
Power supply: | AA battery, 4 pcs |
6
HANDHELD DIGITAL THERMOMETER |
||||
MC1000 SERIES |
.png)
MC1000 is a handheld digital thermometer having an easy-to-read large LCD display and light weight. A range of temperature probes with a variety of shapes and sizes to suit the application requirements.
Dual displays for measured data and arithmetic result
Multi-input (thermocouple/RTD) allows various applications
Exclusive connector prevents accidental probe disconnection
20 data storage
Main Specifications |
Measuring range: | Thermocouple type | K —200 to 1370°C |
T —200 to 400°C | ||
RTD PT100 | —200 to 500°C | |
Display: | 3-1/2 digital LCD with backlight | |
Computation: | Max/min/average/relatives | |
Power supply: | AA battery, 2 pcs | |
Standard: | CE | |
Dimensions: | 76(W)X164(H)X36.3(D)mm |
DIGITAL THERMOMETER |
||||
FOR FOODS |
||||
MODEL MF1000 |
.png)
The portable thermometer Model MF1000 is combined with a needle type sensor for measurement of internal temperature of foods or liquid temperature.
Washable and anti-bacteria surface housing
Main Specifications |
Temperature range: | —40 to 260°C |
Measuring accuracy: | ±0.5°C |
Response time: | 2 seconds |
Sensor: | K type thermocouple |
Sealing: | IP67 (waterproof and dustproof) |
CE conformed |
SHEATH THERMOCOUPLES |
||||
SHEATH RESISTANCE THERMOMETERS |
.png)
The temperature sensors filled with high-purity magnesium oxide in protection tube provide excellent response along with vibration resistance and corrosion resistance.
Main Specifications |
Thermocouple
Class: | JIS 1 (class 0.4), 2 (class 0.75) |
Element: | K, J, E, T |
Measuting temperature: | —200 to 1050°C |
Protection tube diameter: | 0.3, 0.5, 1.0, 1.6, 3.2, 4.8, 6.4, 8.0mm |
Protection tube length: | 300, 500, 750, 1000, 1500, 2000mm |
Protection tube material: | K.-SUS316, SUS310S, SUS347, NCF600 |
J, E, T.-SUS316 | |
(Protection tube of 0.3 and 0.5mm 0 : only | |
available on K element and NCF600) |
Resistance thermometers
Class: | JIS A, B |
Element: | Pt100, JPt100, 3-wire |
Nominal current: | 2mA, 1mADC |
Measuring temperature: | —200 to 500°C |
Protection tube diameter : | 3.2,4.8, 6.4, 8.0mm |
Protection tube length: | 300, 500, 750, 1000, 1500, 2000mm |
Protection tube material: | SUS316 |
ROLLER SURFACE THERMOCOUPLES |
||||
CO15 SERIES |
.png)
The thermocouples are designed for non-contact measurement of surface temperature of moving or rolling materials such as heating rollers, moving belts and plastic sheets.
Built-in compensating circuit for the difference between actual temperature and adjacent atmospheric temperature
Affection-free from emissivity of surface
Main Specifications |
Element: | K thermocouple |
Measuring accuracy: | Within ±5°C in 200°C span |
Measuring distance: | 1 to 2mm (fixed) |
Output: | E.M.F. of K thermocouple |
7
TEMPERATURE CARD LOGGERS |
||||
MR5000 SERIES |
.png)
MR series is a small size and lightweight card logger. Various types of external mounting sensors including a built-in type are available.
A traceability or inspection certificate, which can be used for HACCP or IS09000, is available. (Separate purchase required)
Capable to store up 6000 data per channel
Conforms to CE and IP-64
Main Specifications |
Measuring range: | —40 to 60°C , 0 to 100°C, 50 to 150°C |
Accuracy rating: | ±1.0°C ±1 digit |
(±0.5t ±1 digit for —5 to 50°C) | |
Sensor: | Automatic switchover of built-in/external sensor. External sensor operates |
when it is connected | |
Measuring range of the built-in sensor : —40 to 60°C | |
Number of storing data: | 6000 data (About 8-month data storage at 60-minute measuring interval) |
Storing mode: | Automatic stop mode under specified conditions or endless mode by a PC |
Communications: | Built-in (Connection to a PC through a data readout unit) |
Protection | IP64 |
External dimensions: | 54(W)X110(H)X20.5(D)mm |
Weight: | 95g (Including batteries) |
Power supply | AAA battery, 2 pcs |
Battery life: | Approx. 1 year (At 25°C and 10-minute interval) |
HANDY LOGGER |
||||
MR2041 SERIES |
.png)
Handy logger MR2041 is a palm size data logger, it is capable of storing up to 10000 temperature data per each channel. Power supply of logger is selectable from AA battery or AC adaptor, so it is usable as a portable type logger or fixing type logger.
Using the exclusive software, recording/recalling of data and programming of logging parameters can be executed with logger or through a personal computer.
Input signals : thermocouple K, E, J, T, 0 to 5V, 0 to 20mA
Simultaneous 4 channels, measurement and display
Data process-able through a personal computer
Main Specifications |
Measuring range: | Thermocouple...... | K —200.0 to 1370.0°C |
E —200.0 to 700.0°C | ||
J —200.0 to 700.0°C | ||
T —200.0 to 400.0°C | ||
DC voltage...... | 0 to 5V (scale —9999 to 9999) | |
DC current........ | 0 to 20mA (scale —9999 to 9999) | |
Accuracy rating: | Thermocouple.... | ±(0.1% of measuring value + 0.3°C)(>-100°C) |
0.3°C)(>-100°C) | ||
±(0.1% of measuring value + | ||
0.6°C)(<-100°C) | ||
DC voltage......... | ±(0.1% of measuring value + | |
0.2% of range) |
8
PALM-SIZED |
||||
TEMPERATURE / |
||||
HUMIDITY METER |
||||
HN-CH SERIES |
.png)
The HN-CH series is a reliable and accurate palm-sized temperature/ humidity meter with the humidity range of 0 to 100%RH by using a newly developed capacitance type humidity sensor. The data logging function capable to store each 8000 readings of temperature and humidity into memory is built-in.
Three types of sensors, sensor built-in type, probe type and separated type available for various applications
Main Specifications |
Relative humidity | ||
Sensor: | High-polymer capacitance type | |
Measuring range: | 0 to 100% RH | |
Accuracy rating: | ±2%RH | |
Temperature | ||
Sensor: | Semiconductor type | |
Measuring range: | —10 to 50°C | |
Accuracy rating: | ±0.5°C | |
Data logging: | Temperature and humidity - each 8000 data | |
(16000 data in total) | ||
Display: | Current data, replaying data, parameters | |
Communications interface: | ||
RS232C or RS485 | ||
Power supply | AA battery, 2 pcs |
THYRISTOR REGULATOR |
||||
JU/JW SERIES |
.png)
The JU/JW series of thyristor regulators feature a compact size and light weight and enable high-density installation. Their methods of control include two ways, the phase-angle control and zero-cross control systems. In the phase-angle control systems, the voltage, current and power feedback control types and a type without feedback control are available for the selection of an optimum type according to the characteristics of the heater used.
Compact, lightweight and high-density installation
Phase-angle firing and zero-cross firing are selectable
Setting communication unit displays voltage, current, power and heater measurement values, and enables parameter setup and operation selection.
Prepare heater disconnection alarm and current limiter
Main Specifications (JU) |
Phase: | Single phase |
Rated voltage: | 100, 110, 120, 200, 220, 240, 380, 400, 440V AC (to be specified) |
Rated frequency: | 50/60Hz (automatic selection) |
Rated current: | 10, 20, 30, 50, 75, 100, 150, 200, 250, 300, 400, 500, 750, 1000A (to be specified) |
Main Specifications (JW) |
Phase: | Three phase |
Rated voltage: | 200V AC (200V/220V/240V selectable) |
400V AC (380V/400V/440V selectable) | |
Rated frequency: | 50/60Hz (automatic selection) |
Rated current: | 10, 20, 30, 50, 75, 100, 150, 200, 250, 300, 400, 500, 750, 1000A (to be specified) |
9
SINGER-PHASE |
||||
THYRISTOR REGULATORS |
||||
JB SERIES |
.png)
The small and lightweight thyristor regulators for single-phase loads are characterized with high panel installation density.
Two control systems, a phase-angle firing system for continuous power control and a zero-cross firing system, are built-in and selectable for various applications and power environment.
The applications include small electric furnaces, calibration bath, casting dies heating and heating units for laboratory use.
Main Specifications |
Phase: | Single-phase |
Rated voltage: | 100 to 120 VAC and 200 to 240 VAC |
(selection by terminals) | |
Rated frequency: | 50/60Hz (automatic selection) |
Rated current: | 20, 30, 40, 50, 75, 100A |
Input signal: | 4 to 20mADC, 1 to 5VDC or on-off contact |
Output range: | 0 to 98% of rated voltage |
Minimum load current: | 0.5A (at 98% output) |
Applicable loads: | Resistive load |
Inductive load (transformer primary control | |
and phase control system only) | |
Control system: | Phase-angle firing and zero-cross firing |
(selectable) |
STANDARD |
||||
RADIATION |
||||
THERMOMETER |
||||
IR-RST SERIES |
.png)
Standard Radiation Thermometer IR-RST series has been developed under collaborative research with the National Metrology Institute of Japan (NMIJ), which is applicable for traceability of calibrating • conventional radiation thermometers.
Main Specifications |
Detecting element: | Silicon Photo Diode |
Measuring range: | 400 to 2000°C 10 .9 u m) 3-step selection |
1000 to 3000°C (0.65 um) 3-step selection |
STANDARD RESISTANCE |
||||
THERMOMETERS |
||||
R800 SERIES |
.png)
The standard platinum resistance thermometers, which have been commercialized under the guidance tif National Research Laboratory of Meteorology, conform to International Temperature Scale, 1990 (ITS-90).
From vapor point of helium to freezing point of silver
Main Specifications |
Measuring range: | 13K to 30°C (R800-0) |
90K to 661°C (R800-2) | |
0 to 962°C (R800-3, 3L) | |
90K to 300°C (R800-9) | |
4K to 0°C (R800-4) |
FIXED POINT |
||||
BLACKBODY FURNACES |
||||
IR-RO SERIES |
.png)
The fixed point blackbody furnaces are used to calibrate standard radiation thermometers for comparison calibration of radiation thermometers.
Main Specifications |
Fixed point temperature: | Zinc | 419.527°C |
Aluminum | 660.323°C | |
Silver | 961.78°C | |
Copper | 1084.62°C | |
Reproducibility of freezing points: | Within ±0.1°C | |
Accuracy rating: | Within ±0.3°C |
STANDARD |
||||
THERMOCOUPLES |
||||
C800 SERIES |
.png)
The standard thermocouples are for calibration of thermocouples.
Three kinds of S type, R type and B type thermocouples are available.
Temperature-thermoelectromotive force tables are prepared on request.
Main Specifications |
Element diameter: | 0.5mm |
Measuring range: | Maximum 1100°C (S, R) |
Maximum 1554°C (B) |
BLACKBODY |
||||
FURNACES |
||||
MODELS IR-R24, IR-R26 |
.png)
The comparison type blackbody furnaces were developed jointly with National Research Laboratory of Meteorology for calibration of radiation thermometers and Nkr have large aperture diameters.
Main Specifications |
Temperature range: | 50 to 450°C (low temperature type) |
200 to 1050°C (medium temperature type) | |
Aperture diameter: | 60mm (low temperature type) |
50mm (medium temperature type) |
10
Heat Pipe Type Fixed |
||||
Point Calibration Furnace |
||||
KT-F116 |
.png)
KT-F116 conducts fixed point calibration of resistance thermometer and thermocouple by realizing freezing point of Al and Ag, combing with shield fixed point cell.
Na heat pipe is used for soaking pipe and realize 0.1t p-p/200mm.
No need of gas exchange, adopts shield fixed point cell, which is easy to use.
Able to maintain more than 10 hours of plateau by adjusting furnace temperature.
Main Specifications |
Furnace Operating Temperature Range: | 600 to 1000°C |
Fixed Point Metal: | Al and Ag |
.png)
FUJIOKA FACTORY
The factory has developed and manufactured instrument systems and software as well as measuring, controling and monitoring instruments including recorders, controllers and scanners.
.png)
STANDARD LABORATORY
The standard laboratory has got the approval (approval # 0024) by the national authority as the approved laboratory of calibration for sensors and has performed calibration tests of sensors from outside.
The laboratory has issued the calibration certificates with JCSS mark for temperature sensors, glass thermometers and radiation thermometers.
.png)
KUKI FACTORY
The factory has developed and manufactured radiation thermometers including moisture meters and thickness meters, sensors including temperature, humidity, pressure and level, and thyristor regulators, and has manufactured and engineered total systems, distributed control systems and special application systems.
.png)
HEAD OFFICE
JQA-EM2414
ISO14001
JQA-0656
ISO9001
CHINO CORPORATION
32-8, KUMANO-CHO, ITABASHI-KU, TOKYO 173-8632, JAPAN
Unit J 1600 Shore Road, Naperville
IL60563, U.S.A.
CHINO CORPORATION INDIA
PVT. LTD.
No. 417/418, 4th floor, B-wing,
Shree Nand-Dham,
Sector 11, C.B.D. Belapur,
Navi Mumbai - 400 614 India
KOREA CHINO CORPORATION
296-1 Osan-Ri, Dongtan-Myun,
Hwasung-City, Kyunggi-Do, Korea
* Specifications subject to change without notice.
CHINO INSTRUMENTATION
(KUNSHAN) CO., LTD.
1-10# Suhang Road Shipai Town,
Kunshan Jiangsu, China 215312
SHANGHAI DAHUA-CHINO
INSTRUMENT CO., LTD
615 Ning Qiao Road, Pudong Jin Qjao Export
Processing Zone, Shanghai, China 201206
Cat-No. CGE-05-10 Dec.-'13 0.5 Printed in Japan

Induction Heating
IR-FA series Page 7
DB600 series Page 5
KR2000 series Page 3

Vacuum Furnace
AH4000 series Page 3
KP series Page 6
JJ series Page 11

Film Drying Process
Infrared radiation thermometerIR-CZ series Page 7
IRMA series Pageio
KR2S series Page 3

CHINO LOOP SOLUTION

Metal Forging
KR2000 series Page 3
IR-SA series Page 8
TP series Page 8
Semiconductors

IR-CA series Page 7
NCZ series
JW series Page 11
KP series Page 6
KE series
Continuous Annealing Furnace

CISAS
DB series Page 6
JU series Page 11
KR2/3 series Page 3
RECORDERS
HYBRID MEMORY RECORDER
AH4000 AL4000 SERIES
These recorders are a hybrid recorder which employs bright and clear, easy to view LCD display. Measuring value display is prepared as 1 point display, multi-points simultaneous display and digital display + bar graph display.Various measuring and recording setting can be easily done by front key switch and confirmed by LCD digital display.
• SD card as data storage (512MB, 1GB, 2GB)
• Setting/Recording software available (Standard attached)
■ Main Specifications No. of measuring points:
- Input types:
-
(AL) 6 points (AH) 6, 12, 24 points
(AL/AH) 1 pen, 2 pens, 3 pens, 4 pens
DC voltage, DC current, Thermocouple,
Resistance thermometer - Accuracy rating:
- ±0.1% +1 digit (DC voltage input)
- Chart speed:
- 1 to 1500mm / h (Dotting type)
1 to 600mm / h, 1 to 200mm/min (pen type) - Power supply:
- 100 to 240VAC, 50/60Hz
- Communications:
- Ethernet, RS232C, RS422A, RS485 (Option)
- Dimensions:
- (AL) 144 X 144 X 216mm
(AH) 288 X 288 X 216mm

GRAPHIC RECORDER
KR2000 KR2S SERIES

The recorder can be used for various applications such as data management, research, development, remote and wide range monitoring by utilizing internet environment.
• 6 or 12 channels measurement at sampling rate of 1sec or 100ms
• Simple no-manual operations. Large data memory
■ Main Specifications No. of measuring points:
- Input types:
- 6, 12 points DC voltage, DC current, Thermocouple, Resistance thermometer
- Accuracy rating:
- ±0.1% ±1 digit (DC voltage input)
- Power supply:
- 100 to 240VAC, 50 / 60Hz
- Communications:
- Ethernet, RS232C, RS422A, RS485 (Option)
- Dimensions:
- (KR2000) 144X144X204mm (KR2S) 144X144X235.7mm
GRAPHIC RECORDER
KR3000 KR3S SERIES

As it can be monitored by a web browser display on several com¬ puters on intranet or internet, FTP transfer of data file and E- mail notification are also available.
• Max large sized 12.1" TFT color LCD touch panel display
• Large capacity of data memory and various recording method
• Multi points recording with high speed/high accuracy
■ Main Specifications No. of measuring points:
- Input types:
- 12, 24,36 and 48 channels DC voltage, DC current, Thermocouple, Resistance thermometer
- Accuracy rating:
- ±0.1 % ±1 digit (DC voltage input)
- Power supply:
- 100 to 240VAC, 50 / 60Hz
- Communications:
- Ethernet, RS232C, RS422A, RS485 (Option)
- Dimensions:
- (KR3000) 288X288X218mm (KR3S) 288X288X180mm
RECORDING AND DATA LOGGING
HYBRID RECORDER
KH4000 KL4000 SERIES
Not only can each measured value be read from the custom made analog scale plate which incorporates input type and measurement value input, but a comprehensive LED display also enables precise digital measurements to be taken by the user.
■ Main Specifications
No. of measuring points:
- Input types:
- (KL) 6 points (KH) 6, 12, 24 points DC voltage, DC current, Thermocouple, Resistance thermometer
- Accuracy rating:
- ±0.1% ±1 digit (DC voltage input)
- Power supply:
- 100 to 240VAC, 50 / 60Hz
- Communications:
- Ethernet, RS232C, RS422A, RS485 (Option)
- Dimensions:
- (KL) 144 X 144 X 216mm
(KH) 288 X 288 X 216mm
HYBRID RECORDER
LE5000 SERIES
Innovative design high performance recorder provides high accuracy ±0.05%; high speed sampling 0.1 second for 36 points and high speed recording, 3 seconds/line. Simple operational keys and PC setting functions drastically improved usability of recording system.
• High speed sampling at 0.1 sec for 36 points and high-speed recording
• Operation keys are functionally designed for ease of use
• High accuracy of 0.05%
■ Main Specifications No. of measuring points:
- Input signals:
- 12, 24 or 36 channels DC voltage 8 kinds, Thermocouple 28 kinds, Resistance thermometer 8 kinds, DC current (shunt resistors)
- Accuracy ratings:
- ±0.05% ±1 digit (DC voltage)
- Power supply:
- 100 to 240VAC, 50/60Hz
- Communications:
- Ethernet, RS422A, RS485 (option)
ANALOG RECORDERS EH3000 EL3000 ES600 SERIES

•Various options for many applications
•High accuracy on 180mm industrial recorders
• Robust analog recorders

•Small and light-weight
•Various models and options

•Small and light-weight (depth-200mm)
•Reliable self-balancing type
- Input types:
- (EH3000 DOT) 1 to 12 points (EH3000/EL3000 PEN) 1 to 3 pens (EL3000 DOT) 1 to 6 points DC voltage, DC current, Thermocouple, Resistance thermometer
- Accuracy rating:
- (EH) ±0.25% ±1 digit (DC voltage input)
(EL) ±0.5% ±1 digit (DC voltage input) - Power supply:
- 100 to 240VAC, 50 / 60Hz
- Input types:
- 1 to 6 points, 1 pen DC voltage, DC current, Thermocouple, Resistance thermometer
- Accuracy rating:
- ±1.0% ±1 digit
(DC voltage input) - Power supply:
- 100to240VAC
50 / 60Hz
DIGITAL INDICATING CONTROLLERS
DIGITAL INDICATING CONTROLLERS
LT/LTA SERIES
• Large easy-to-view 5 digit display
•Highly-functional operation screen and setting screen
•Simple program(4 patterns, 12 steps) ■ Main Specifications
- Input type :
-
Thermocouple
(B,R,S,K,E,J,T,N,others)
Resistance thermometer
(Pt100, JPt100,Pt50)
DC voltage
(±20mV,±100mV,±5V,±10V) - Accuracy rating :
- ±0.1% of FS ± 1 digit of measuring range
- Control system :
- PID system or Z control
- Output type :
-
ON-OFF pulse output, ON-OFF servo
output (DB650 and DB670 only),
Current output, SSR drive pulse
output, Voltage output - Power supply :
- 100 to 240VAC or 24VAC/24VDC
- Communication interface:
- Dimensions:
-
DB670 RS422A, RS485(option)
DB650 RS422A, RS485(option)
DB630 RS485(option)
DB670 96 x 96 x 73mm
DB650 48 x 96 x 73mm
DB630 48 x 48 x 88mm
DIGITAL INDICATING CONTROLLERS
DB600 SERIES
LT110 |
LT230 |
LT23A |
LT35A/37A |
LT45A/47A | |
Input type |
K,E,J,N |
B,R,S,N,K,E,J,T,U,L | |||
Resistance thermometer |
Pt100,JPt100 | ||||
DC voltage |
— |
±5V | 0 to 5V | |||
DC current |
— |
4 to 20mA | |||
Accuracy rating |
±0.3% of |
±0.25% |
±0.5% |
±0.2% |
±0.1% |
Resistance Thermometer |
±0.2% of | ||||
Sampling |
250msec |
500msec |
500msec |
300msec |
100msec |
Control system |
PID system |
PID system | |||
Output type |
ON-OFF pulse, SSR drive pulse, Current output |
ON-OFF pulse, SSR drive pulse, | |||
Power supply |
100 to |
100 to 240VAC |
100to240VAC 21.6to26.4VDC | ||
Dimensions (mm) |
96x96 |
48x48 |
48x48 |
48 x 96 x 65 / |

EASY-TO-OPERATE AND ABUNDANT FUNCTIONS
DIGITAL INDICATING CONTROLLERS
DB SERIES

Various function including universal input and multiple setting values (8 types) are provided as standard.
• Large easy-to-view 5 digit display
• Highly-functional operation screen and setting screen
• Outstanding controllability
• Conforming to international safety standards and
CE marking and conforming to RoHS
■ Main Specifications
- Input type :
- Thermocouple (B,R,S,K,E,J,T,N,others) Resistance thermometer (Pt100, Pt-Co,others) DC voltage (±10mV,±20mV,±50mV,±100mV, ±5V,±10V)
- Accuracy rating :
- ±0.1% of measuring range ± 1 digit
- Control system :
- PID system or Z control
- Output type :
- ON-OFF pulse, ON-OFF servo, Current output, SSR drive pulse, Voltage output
- Power supply :
- 100 to 240VAC or 24VAC/24VDC
- Communication interface :
- RS232C, RS422A, RS485(option)
- Dimensions:
- 96 x 96 x 127mm
PROGRAM CONTROLLERS
KP SERIES

Various function including the whole program pattern display screen and universal input are provided as standard.
• Large easy-to-view 5 digit display
• Highly-functional operation screen and setting screen
• Easily identifiable pattern progress display
• Outstanding controllability
• Conforming to international safety standards and CE marking and conforming to RoHS
■ Main Specifications
- Input type :
-
Thermocouple (B,R,S,K,E,J,T,N,others)
Resistance thermometer (Pt100,Pt-Co,others)
DC voltage (±10mV,±20mV,±50mV,±100mV, ±5V,±10V) - Accuracy rating :
- ±0.1% of measuring range ± 1 digit
- Control system :
- PID system
- Output type :
- ON-OFF pulse, ON-OFF servo, Current output, SSR drive pulse, Voltage output
- Power supply :
- 100 to 240VAC or 24VAC/24VDC
- Communication interface :
- RS232C, RS422A, RS485 (option)
- Dimensions:
- 96 x 96 x 127mm
DIGITAL INDICATING CONTROLLERS
CP SERIES

• Adopt MODBUS communications mode, CE marking
• Universal power supply (100-240V AC)
• More programmed control mode
• Can select the PID mode from total PID type or differential type ■ Main Specifications
- Input type :
- Thermocouple (B,R,S,K,E,J,T,N,others) Resistance thermometer (Pt100,JPt100) DC voltage (±5V)
- Accuracy rating :
- ±0.25% of measuring range ± 1 digit
- Control system :
- PID system
- Output type :
- ON-OFF pulse, Current output, SSR drive pulse, Voltage out put
- Power supply :
- 100 to 240VAC
- Dimensions:
- CP350...48 x 96 x 132 mm CP370...96 x 96 x 132 mm
PROGRAM CONTROLLERS
DP-G SERIES
• Easy program pattern setting on graphic screen
• High performance and universal input
• Storing settings in CF card ■ Main Specifications
- Input type :
- Thermocouple (B,R,S,K,E,J,T,N,others) Resistance thermometer (Pt100, JPt100,others) DC voltage (±10mV,±20mV,±50mV,±100mV, ±5V,±10V) DC current(20mA)
- Accuracy rating :
- ±0.1% of measuring range ± 1 digit (DC voltage/current input)
- Control system :
- PID system
- Output type :
- ON-OFF pulse type, ON-OFF servo type , Current output type, SSR drive pulse type, Voltage output type
- Power supply:
- 100 to 240VAC ,50/60Hz
- Dimensions:
- 144 x144 x252mm
INFRARED RADIATION THERMOMETERS
HIGH-SPEED INFRARED RADIATION THERMOMETER
IR-CZ SERIES

• High response, 2 to 15ms
• Significantly effective for distinctive applications:
— Ceramic high-temp, baking process
— Crystal growing
■ Main Specifications Temperature range:
350 to 2000°C / 400 to 3100°C / 500 to 3500°C
Response time: 2 to 15ms
Analog output: 4 to 20mADC
INFRARED RADIATION THERMOMETER
INFRARED RADIATION THERMOMETER

• Functional digital display and parameter setup keys
• High accuracy, high-speed response, high reliability
• High distance factor in focusable model to enable ease of installation
• Optional RS485 communications
• Remote setup and monitoring by IR-GZ connectable up to 32 IR-CA
• Software package IR-VXC1E
• Variety of accessories to protect the IR-CA under harsh environment
INFRARED RADIATION THERMOMETER
IR-BA SERIES

A standard speed type and a high speed type (50ms/95%) are respectively available for these standard type and small-target/short-distance type and small-target/long-distance type, and also various applicable types like as glass, lamp-anneal, film and burning gas. • High response: Standard: 100ms, High-speed: 50ms
• Compact & lightweight: W32XH56XD100mm, 220g
■ Main Specifications Detecting element/measuring wavelength: Thermopile Temperature range:
0 to 300°C, 0 to 600°C
Output: 4 to 20mADC
Power supply: 12 to 24VDC
FIBER OPTIC RADIATION THERMOMETER
IR-FA SERIES

• Low temperature type with high-speed response and short wavelength enables to measure objects with low emissivity like as metals.
• Medium/high temperature type with high accuracy ±0.5 to 1% for 1000 to 2000°C) and high-speed response is for various temperature measurement fields.
• Two-color type is stable with less effectiveness of smoke, vapor, dust and lack-of-view.
■ Main Specifications Detecting element/measuring wavelength:
Single-color type: PbS/ 2.0pm, InGaAs / 1.55pm, Si/0.9pm,
Two-color type: Hybrid element 0.9 / 1.55pm,
Output: 4 to 20mADC
Power supply: 24VDC
FURNACE MONITORING SYSTEM
CPA-R SERIES

The special high temperature optics lens array system can be inserted through a small insertion hole on many types of furnaces. The image processing unit has an 8.3" LCD touch panel that displays wide-angle image and temperature information. It also provides the capability of up to 40 points of contact Inputs/outputs as well as 32 points of analog outputs through an external I/O unit.
Wavelength: 0.8 to 1.0pm
Temperature range: 700°C to 2500°C
(Assignable span:200°C to 500°C)
Accuracy: ±1% at full scale (black body)

Camera control: Up to 3 Cameras
Display: 8.4” Color LCD (touch panel)
External input/output: Contact output max 40 points
Protective Structure: IP65 (Front Panel)
NON-CONTACT TEMPERATURE MEASUREMENT
PALM SIZED
INFRARED RADIATION THERMOMETER
IR-TE2

Model IR-TE2 palm-sized infrared thermometer is designed to measure the surface temperature of objects without making contact with them. The built-in laser sighting pinpoints the center of the area being measured on the target.
• Conforms to IP67 (dustproof and waterproof) and washable.
• ABS resin housing with sanitary specification fits in your safety program. CE marking
• Wide temperature range of -40 to 300°C (-40 to 572°F) - °C/°F selectable
ON-LINE INFRARED RADIATION THERMOMETER
IR-SA SERIES

• Fast response time of 0.002 seconds for IR-SAI/IR-SAS
• RS485 MODBUS connectivity
• Telescope or laser pointer for targeting
HAND-HELD TYPE
INFRARED RADIATION THERMOMETER
IR-TAP

• Temperature range: -40 to 500°C
• Spot size: Ø30 / 1000mm
• CE marking
RADIATION THERMOMETER
IR-H SERIES

• Temperature range from 400°C to 3000°C (IR-HQH)
• CE marking
• Low temperature area and emissivity are measured by connecting a K-type thermocouple separately prepared.
■ Main Specifications
Detecting element: Si (IR-HS), InGaAs (IR-HI), Si/InGaAs (IR-HQH)
Response time: 0.2 seconds
Power supply: 2AA batteries
RADIATION DIGITAL THERMOMETER
IR-AH SERIES

• A data logging software package for easy data treatment
• CE marking
■ Main Specifications
Detecting element: Si, Thermopile
Power supply: 4AA batteries
THERMAL IMAGING SENSOR
HAND-HELD TYPE THERMAL IMAGING SENSOR
TP-S

• Temp.range of -10 to 180°C
• 2000 pixel resolution
• Just one click operation and instant glance
• Temperature range: -10 to 180°C
• ABS resin(anti bacterial)
• CE marking
THERMAL IMAGING SENSOR
TP SERIES

• Easy to use and implement
• 2000 pixel resolution
• Built-in alarms
• IP65/NEMA4, CE marking
■ Main Specifications
Temperature range: -20 to 300°C,100 to 800°C
Resolution: 0.5°C (At black body temperature of 100°C)
Accuracy: ±2% of reading or ±3°C whichever lager
(At ambient temp of 25°C±2°C)
Power supply: 12 to 24VDC
THERMAL IMAGING SYSTEM
CPA-L SERIES

The camera, supporting measuring wavelengths of 8 to 14pm and a temperature detecting range of -40°C to 500°C, is compact, lightweight, and excellent in dust and drip proofing performance.
The controller has image processing functions such as binarization and particle analysis functions in addition to the temperature measurement processing function and can provide output via a LAN and as analog/digital signals.
TEMPERATURE / HUMIDITY SENSORS

HANDHELD TYPE TEMPERATURE/HUMIDITY METER
HN-EH SERIES
Speedy, lightweight, high accuracy!!Measurement in 30-seconds level !!
• Overriding fast response time, measurement 30-seconds level
• Small, lightweight (sensor built-in type approx. 120g) and easy operation
• Low running cost, built-in type sensor unit is interchangeable by user
■ Main Specifications Measuring range:
Temperature
-10 to 45°C (Sensor built-in type)
-20 to 70°C (Probe type)
Relative humidity 5 to 95%RH (no dew condensation)
Dew point temperature -35 to 55°C (standard type only)
Measuring resolution:
Temperature 0.1°C, Relative, humidity 0.1 %RH
Response: Temperature 40 seconds or less (under 0.5m/s ventilation, 90% step response of approx.50°C->25°C) Humidity
40 seconds or less (25°C constant, under 0.1 m/s ventilation, 90% step response of approx.30%RH->50%RH)
Standard: CE marking
DIGITAL THERMOMETER FOR FOODS
MODEL MF1000

• Washable and anti-bacteria surface housing
■ Main Specifications Temperature range: -40 to 260°C
Measuring accuracy: ±0.5°C
Response time: 2 seconds
Sensor: K type thermocouple
Sealing: IP67 (waterproof and dustproof)
Standard: CE marking
ROLLER SURFACE THERMOCOUPLES
C015 SERIES
The thermocouples are designed for non-contact measurement of surface temperature of moving or rolling materials such as heating rollers, moving belts and plastic sheets.PALM-SIZED TEMPERATURE/HUMIDITY METER
HN-CH SERIES

• Three types of sensors, sensor built-in type, probe type and separated type available for various applications ■ Main Specifications Relative humidity
Sensor: High-polymer capacitance type
Measuring range: 0 to 100% RH Accuracy rating: ±2%RH (0 to 90%RH at 25°C)
Temperature
Sensor: Semiconductor type
Measuring range: -10 to 50°C Accuracy rating: ±0.5°C (0 to 50°C)
Data logging: Temperature and humidity -each 8000
data (16000 data in total)
Display: Current data, replaying data, parameters
Communications interface: RS232C or RS485 Power supply: 2AA batteries or 100-240 V AC (with AC adapter; sold separately)
Standard: CE marking
•Affection-free from emissivity of surface
■ Main Specifications Element: K type thermocouple
Measuring accuracy: Within ±5°C in 200°C span Measuring distance: 1 to 2mm (fixed)
Output: E.M.F. of K type thermocouple
SELECTION FROM VARIOUS SENSORS FOR EACH APPLICATION
HANDHELD DIGITAL THERMOMETER
MC1000 SERIES

A range of temperature probes with a variety of shapes and sizes to suit the application requirements.
• Dual displays for measured data and arithmetic result
• Multi-input
(thermocouple/RTD) allows various applications • Exclusive connector prevents accidental probe disconnection ■ Main Specifications Measuring range:
Thermocouple type K -200 to 1370°C
T -200 to 400°C
RTDPT100 -200 to 500°C
Display: 3-1/2 digital LCD with backlight
Computation: Max/min/average/relatives
Power supply: 2AA batteries
Standard: CE marking
Dimensions: 76(W) X 164(H) X 36.3(D)mm
THERMO HYGROMETER
HN-C SERIES

Wall-mount type, separated type and inserting type are available for various application. Heat-resistive and separated type, which can be used in operating temperature of -40 to 180°C is available, too.
■ Main Specifications Humidity
Measuring range: 0 to 100% (no dew condensation)
Accuracy range: ±2%RH (at 0 to 90%RH and 25°C)
±3%RH (at 90 to 95%RH and 25°C) Coefficient of relative humidity / temperature:
±0.1 %RH / °C (at 5 to 80°C)
Temperature
Measuring range:-40 to 180°C
Accuracy range: ±0.3°C (±0.5°C Heat-resistive separated type)
TEMPERATURE CARD LOGGER
MR SERIES

• A traceability or inspection certificate, which can be used for HACCP or IS09000, is available. (Separate purchase required)
• Capable to store up 6000 data per channel
• Conforms to CE marking and IP64
■ Main Specifications Measuring range:-40 to 60°C, 0 to 100°C, 50 to 150°C
Accuracy rating: ±1.0°C ±1 digit
(±0.5°C ±1 digit for -5 to 50°C)
Sensor: Automatic switchover of built-in/external sensor.
External sensor operates when it is connected Measuring range of the built-in sensor: -40 to 60°C
Number of storing data:
6000 data (about 8-month data storage at 60-minute measuring interval)
Storing mode: Automatic stop mode under specified conditions
or endless mode by a PC
Communications: Built-in (connection to a PC through a data readout unit)
Standard: IP64, CE-marking
External dimensions: 54(W) X 110(H) X 20.5(D)mm
Weight: 95g (including batteries)
Power supply: 2AAA batteries
Battery life: Approx. 1 year (at 25°C and 10-minute interval)
HANDY LOGGER
MR2041 SERIES

Using the exclusive software, recording/recalling of data and programming of logging parameters can be executed with logger or through a PC.
• Input signals: thermocouple, K, E, J,T, 0 to 5V, 0 to 20mA
• Simultaneous 4 channels, measurement and display
• Data processable through a PC
■Main Specifications Measuring range:
Thermocouple
K -200.0 to 1370.0°C
E -200.0 to 700.0°C
J -200.0 to 700.0°C
T -200.0 to 400.0°C
DC voltage
0 to 5V (scale -9999 to 9999)
DC current
0 to 20mA (scale -9999 to 9999)
Accuracy rating:
Thermocouple
±(0.1% of measuring value + 0.3°C>-100°C)
±(0.1 % of measuring value + 0.6°C<100°C)
DC voltage
(0.1% of measuring value +0.2% of range)
ON-LINE MEASUREMENT OF INFRARED MULTI ANALYZER, MOISTURE (THICKNESS) METERS
INFRARED MULTI ANALYZER
IM SERIES
The IM series is on-line multi analyzer utilizing the infrared absorption. Converting capabilities are built into the compact designed detector unit for easy installation and operation.• Ethernet, MODBUS communications
• High-speed & High-repeatability (28ms)
• Self-diagnostic function, easy maintenance ■ Main Specifications Measuring system: Infrared reflection type
Measuring wavelength: Up to 10 wavelengths Measuring scope: Up to 4 constituents
Computing function: Ratio calculation for 2-color or 3-color, and multiple regression calculation
Calibration curve: Linear, quadratic, cubic and multiple regression line

ELECTRIC HEATERS CONTROL AND TEMPERATURE SENSORS
THYRISTOR REGULATORS
SINGLE/THREE-PHASE THYRISTOR REGULATORS
JU/JW SERIES

• Compact, lightweight and high-density installation
• Phase-angle firing and zero-cross firing are selectable
• Setting communication unit displays voltage, current, power and heater measurement values, and enables parameter setup and operation selection
• Prepare heater disconnection alarm and current limiter
■ Main Specifications JU
Phase: Single phase
Rated voltage: 100, 110, 120, 200, 220, 240, 380,
400, 440V AC (to be specified)
Rated frequency: 50/60Hz (automatic selection)
Rated current: 10, 20, 30, 50, 75, 100, 150, 200, 250,
300, 400, 500, 750, 1000A (to be specified)
JW
Phase1 Three phese
Rated voltage: 200V AC (200V/220V/240V selectable)
400V AC (380V/400V/440V selectable) Rated frequency: 50/60Hz (automatic selection)
Rated current: 10, 20, 30, 50, 75, 100, 150, 200, 250, 300,
400, 500, 750, 1000A (to be specified)
SINGLE-PHASE THYRISTOR REGULATORS
JB SERIES

THYRISTOR REGULATORS
JJ SERIES

Coming soon!
• Easy setting for parameter such as elevation, soft-start and so on
• Outputs data to PLC or PC with communication function (option) and parameter can be changed from host unit
• Alarm contents are displayed when alarm is activated. Output alarm contact from AL1 and AL2 depending on the situation
• Phase-angle firing and zero-cross firing are selectable
• Switching between feedback and non-feedback of voltage, current and power in phase angle firing are possible
• Switching between fixed time base and variable time base in zero cross firing are possible
• Heater disconnection alarm and current limiter is available as option
• CE marking will be conformed.

Rated voltage: 100 to 120 VAC and 200 to 240 VAC
(selection by terminals)
Rated frequency: 50/60Hz (automatic selection)
Rated current: 20, 30, 40, 50, 75, 100A (to be specified)
Input signal: 4 to 20mADC, 1 to 5VDC or on-off contact
Output range: 0 to 98% of rated voltage
Minimum load current:
0.5A (at 98% output)
Applicable loads: Resistive load
Inductive load (transformer primary control and phase control system only)
Control system: Phase-angle firing and zero-cross firing (selectable)
SHEATH THRM0C0UPLES SHEATH RESISTANCE THRM0METERS
The temperature sensors filled with high-purity magnesium oxide in protective tube provide excellent response along with vibration resistance and corrosion resistance.■ Main Specifications Thermocouples
Class: JIS 1 (class 0.4), 2 (class 0.75)
Element: K, J, E, T, N, Chino Array B (NB), X (XL)
Measuting temperature: -200 to 1050°C Protective tube diameter: 0.15,0.3, 0.5,1.0,1.6, 3.2,4.8,6.4, 8.0mmØ
Protective tube length: 300, 500, 750, 1000, 1500, 2000mm~
Protective tube material: SUS316, SUS310S, NCF600
J, E, T-SUS316
(Protection tube of 0.3 and 0.5mmØ
: only available on K element and NCF600)

Class: JIS A, B
Element: Pt100, JPt100, 3-wire
Nominal current: 2mA, 1mADC
Measuring temperature: -200 to 500°C Protection tube diameter: 3.2, 4.8, 6.4, 8.0mmØ
Protection tube length: 300, 500, 750, 1000,1500, 2000mm
Protection tube material: SUS316
STANDARD SENSORS AND RADIATION THERMOMETERS
TRACEABILITY
SMALL TYPE LOW TEMPERATURE COMPARATIVE CALIBRATION EQUIPMENT
KT-H SERIES
Realize low temperature calibration at -100°C and compact & light weight body.For on-site calibration of resistance thermometer and thermocouple!
■ Main Specifications Calibration Temperature Range : -100 to 50°C (KT-H503)
-30 to 155°C (KT-H504)
-20 to 155°C (KT-H504S)

FIXED POINT BLACKBODY FURNACE
IR-ROA SERIES

IR-ROA is a highly precise fixed point black body furnace that can use for the temperature standard for radiation thermometer. IR-ROA has 6 kinds of fixed point cell from In (157°C) in low temperature to Cu(1085°C) in high temperature.
• Realization of a good plateau by the improvement of the temperature distribution
• Lineup In to Cu point
• Changeable to other fixed points by cell exchange easily
• Compact size (184 X 370 X 360mm), weight (13kg)
■ Main Specifications Fixed point cell In point: 156.60°C, Sn point: 231.93°C
Zn point: 419.53°C, Al point: 660.32°C
Ag point: 961.78°C, Cu point: 1084.62°C
COMPARISON BLACKBODY
MODELS IR-R24,IR-R26,IR-R27 FURNACE

■ Main Specifications Temperature range: 50 to 450°C (low temperature type)
200 to 1050°C (medium temperature type)
800°C to 1450°C (high temperature type)
Aperture diameter: 060mm (low temperature type)
050mm (medium temperature type) 030mm (high temperature type)
STANDARD RADIATION THERMOMETER
IR-RST SERIES

Measuring range: 400 to 2000°C (0.9^m) 3-step selection
1000 to 3000°C (0.65/^m) 3-step selection
150 to 1100°C (1,6jum) 3-step selection
HEAT PIPE TYPE FIXED POINT CALIBRATION FURNACE KT-F116 KT-F116 conducts fixed point calibration of resistance thermometer and thermocouple by realizing freezing point of Al and Ag, combing with shield fixed point cell.
• Na heat pipe is used for soaking pipe and realize 0.1°C p-p/200mm.
• No need of gas exchange,adopts shield fixed point cell, which is easy to use.
• Able to maintain more than 10 hours of plateau by adjusting furnace temperature. ■ Main Specifications Furnace operating temperature range: 600 to 1000°C
Fixed point Metal: Al and Ag
STANDARD RESISTANCE THERMOMETER
R800 SERIES
The standard platinum resistance thermometers, which have been commercialized under the guidance of National Research Laboratory of Metrology, conform to International Temperature Scale, 1990 (ITS-90).• From vapor point of helium to freezing point of silver
■ Main Specifications Measuring range: 13K to 30°C (R800-0), 90Kto 661 °C (R800-2)
0 to 962°C (R800-3, 3L), 4K to 0°C (R800-4)

STANDARD THERMOCOUPLE
C800 SERIES
The standard thermocouples are for calibration of thermocouples. Three kinds of S type, R type and B type thermocouples are available.• Temperature-thermoelectromotive force tables are prepared on request. ■ Main Specifications Element diameter: Ø0.5mm
Measuring range: Maximum 1100°C(S, R)
Maximum 1554°C(B)


TEMPERATURE CAURRATION EQUIPMENT

For to maintain temperature accuracy
We provide abundant thermometer calibration equipment such as thermocouple, resistance thermometer, infrared thermometer and glass thermometer to assist traceable measurement at customers’ site. Traceability is required for thermometers used in various industries such as research, production, inspection and distribution because of quality control, ISO, HACCP, safety and maintaining accuracy.CHINO prepares calibration equipments, measurement instruments and standard sensors for thermocouples, resistance thermometers, infrared thermometers, glass thermometers for to assist to establish customers’ traceability systems. These are used in widely used in each industry and testing/research institute.




Trusted Network
We provide calibration at each part of the world for to support every one of you.


CHINO CORPORATION
32-8, Kumano-cho, Itabashi-ku, Tokyo 173-8632, JapanCat.No.CXE-31-02 Aug.'13 (D Printed in Japan